1. Specifications
1-2 Major Component Specifications
(B) Outdoor Unit
MODEL No. CH2442
Source 230 - 208 VAC / 1 phase / 60 Hz
Controller P.C.B. Ass'y CR - CH2442 (Microprocessor)
Control circuit fuse 250 VAC, 3 A
Compressor Rotary (Hermetic)
Model C - 2R160H6T
Source 230 - 208 VAC / 1 phase / 60 Hz
Nominal output W 1,700
Compressor oil cc 800
Coil resistance (Ambient temperature 77 °F) C – R : 0.885 , C – S : 1.773
Safety device Internal type
Overload relay models
Operating temperature Open °F297± 9
Close °F198± 20
Operating ampere (at 77 °F) A
Run capacitor VAC, µF 400 VAC, 40 µF
Crank case heater VAC, W 230 VAC, 30 W
Refrigerant amount charged at shipment lbs. (kg) R22 : 6.17 (2.8)
High pressure switch ACB
-
1UB11
Set pressure OFF lb/in
2
(kg/cm
2
) 426.6 (30 )
ON lb/in
2
(kg/cm
2
) 341.3 ± 28.44 (24 ± 2.0)
Fan Propeller
Number...diameter in. (mm) 1 ... 18 - 3/32 (460)
Fan speeds 2 (AUTO)
Fan motor
Model KFC6T - 91D6P
Source 230 - 208 VAC / 1 phase / 60 Hz
No. of pole ..... rpm (230 V, High) 6 ... 879
Nominal output W 110
Coil resistance BRN WHT : 67.14 , VLT YEL : 11.42
(Ambient temperature 68 °F) WHT VLT : 64.85 , YEL PNK : 10.60
Safety device Internal type
Operating temperature Open °F248± 9
Close °F171± 27
Run capacitor VAC, µF 440 VAC, 4 µF
Heat exchange
Coil Aluminum plate fin / Copper tube
Rows ..... Fins per inch 2 ... 14.1
Face area ft.
2
(m
2
) 6.78 (0.63)