IMPORTANT
These air conditioners employ new
refrigerant R410A.
Pay special attention when
servicing the unit.
Wall mounted type
KMS0772
KMS0972
KMS1272
KMS1872
KMS2472
< Applicable Indoor Units >
TECHNICAL & SERVICE MANUAL
OUTDOOR UNIT : CM1972
CM2472
CM3172
DC INVERTER MULTI-SYSTEM AIR CONDITIONER
Destination: North America
Product Code No.
1 852 330 27
1 852 330 28
1 852 330 29
REFERENCE NO.
SM700666-04
Capacity at 230V
19,700 BTU/h
25,400 BTU/h
30,600 BTU/h
Outdoor Model No.
CM1972
CM2472
CM3172
NOTE
CM1972
CM2472
CM3172
For details about the combination, refer to
"Unit Combination Table" in the Appendix
of this manual.
FILE NO.
Page view 0
1 2 3 4 5 6 ... 98 99

Summary of Contents

Page 1 - OUTDOOR UNIT : CM1972

IMPORTANTThese air conditioners employ newrefrigerant R410A.Pay special attention whenservicing the unit.●Wall mounted type KMS0772 KMS0972 K

Page 2 - Please Read Before Starting

Outdoor Unit CM3172Indoor Unit KMS0972 × 4< 230V >Remarks:1. The values shown in performance section and electrical rating section above are ba

Page 3 - Table of Contents

Outdoor Unit CM3172Indoor Unit KMS0972 × 4< 208V >Remarks:1. The values shown in performance section and electrical rating section above are ba

Page 4 - APPLICABLE INDOOR UNITS

Outdoor Unit CM19722-2-1. Outdoor UnitControl PCBControl Circuit Fuse ControlsPart No.Microprocessor250V 25ACB-CM1972DATA SUBJECT TO CHANGE WITHOUT N

Page 5 - 1. OPERATING RANGE

Outdoor Unit CM2472Control PCBControl Circuit Fuse ControlsPart No.Microprocessor250V 25ACB-CM2572DATA SUBJECT TO CHANGE WITHOUT NOTICE.Pints (cc) - M

Page 6 - 2. SPECIFICATIONS

Outdoor Unit CM3172Control PCBControl Circuit Fuse ControlsPart No.Microprocessor250V 25ACB-CM3172DATA SUBJECT TO CHANGE WITHOUT NOTICE.Pints (cc) - M

Page 7 - Outdoor Unit CM1972

Temperature F ( C)4035302520151050(-20)(-15)(-10) (-5) (0) (5) (10) (15) (20)-4514 23 32 41 50 59 68Resistance (k ohm)032 50 68 86 104 122 140 158 1

Page 8

Wide tube service valvedia.3/8" (9.52) × 3Narrow tube service valvedia.1/4" (6.35) × 34-7/165-29/32 2-27/32 2-3/42-1/32 4-1/22-15/162-3/429-

Page 9

Wide tube service valvedia.3/8" (9.52) × 3Narrow tube service valvedia.1/4" (6.35) × 4Wide tube service valvedia.1/2" (12.70) × 14-7/16

Page 10 - < 230V >

Wide tube service valvedia.3/8" (9.52) × 2Narrow tube service valvedia.1/4" (6.35) × 4Wide tube service valvedia.1/2" (12.70) × 24-7/16

Page 11 - < 208V >

CompressorHigh pressureswitchH.P.MainaccumulatorSubaccumulatorService valve onnarrow tubeService valve onwide tubeCNBNANCWBWAWO.D.1/4"O.D.1/4&quo

Page 12 - 2-2-1. Outdoor Unit

When WiringELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM.SP

Page 13 - Outdoor Unit CM2472

Outdoor Unit CM2472Insulation of Refrigerant TubingBecause capillary tubing is used in the outdoor unit, both thewide and narrow tubes of this air co

Page 14

Service valve onnarrow tubeElectric expansion valveService valve onwide tube DNCNBNANDWCWBWAWO.D.1/4"O.D.1/4"O.D.1/4"O.D.1/4"O.D.3

Page 15

Cooling Characteristics(RH : 46%, Indoor fan speed : High fan)(230V, 60Hz)(1) Low pressure performance chart(2) Operating current performance chart(3)

Page 16 - 3. DIMENSIONAL DATA

Cooling Characteristics(RH : 46%, Indoor fan speed : High fan)(230V, 60Hz)(1) Low pressure performance chart(2) Operating current performance chart(3)

Page 17 - Outdoor Unit CM2472

Outdoor Unit CM1972 Indoor Unit KMS1272 × 1Cooling Characteristics(RH : 46%, Indoor fan speed : High fan)(230V, 60Hz)(1) Low pressure performan

Page 18 - Outdoor Unit CM3172

Cooling Characteristics(RH : 46%, Indoor fan speed : High fan)(230V, 60Hz)(1) Low pressure performance chart(2) Operating current performance chart(3)

Page 19 - 4. REFRIGERANT FLOW DIAGRAM

Cooling Characteristics(RH : 46%, Indoor fan speed : High fan)(230V, 60Hz)(1) Low pressure performance chart(2) Operating current performance chart(3)

Page 20 - Indoor unit Outdoor unit

Cooling Characteristics(RH : 46%, Indoor fan speed : High fan)(230V, 60Hz)(1) Low pressure performance chart(2) Operating current performance chart(3)

Page 21

Outdoor Unit CM2472 Indoor Unit KMS1272 × 1Cooling Characteristics(RH : 46%, Indoor fan speed : High fan)(230V, 60Hz)(1) Low pressure performan

Page 22 - 5. PERFORMANCE DATA

Cooling Characteristics(RH : 46%, Indoor fan speed : High fan)(230V, 60Hz)(1) Low pressure performance chart(2) Operating current performance chart(3)

Page 23 - 75°F (24°C)

Table of Contents45612151619223639424547484950545556575758606161A-1A-2...

Page 24 - Cooling Characteristics

Cooling Characteristics(RH : 46%, Indoor fan speed : High fan)(230V, 60Hz)(1) Low pressure performance chart(2) Operating current performance chart(3)

Page 25

Cooling Characteristics(RH : 46%, Indoor fan speed : High fan)(230V, 60Hz)(1) Low pressure performance chart(2) Operating current performance chart(3)

Page 26

Cooling Characteristics(RH : 46%, Indoor fan speed : High fan)(230V, 60Hz)(1) Low pressure performance chart(2) Operating current performance chart(3)

Page 27

Cooling Characteristics(RH : 46%, Indoor fan speed : High fan)(230V, 60Hz)(1) Low pressure performance chart(2) Operating current performance chart(3)

Page 28

146(1.0)174(1.2)118(0.8)90(0.6)Cooling Characteristics(RH : 46%, Indoor fan speed : High fan)(230V, 60Hz)(1) Low pressure performance chart(2) Operati

Page 29

146(1.0)174(1.2)118(0.8)90(0.6)Cooling Characteristics(RH : 46%, Indoor fan speed : High fan)(230V, 60Hz)(1) Low pressure performance chart(2) Operati

Page 30

Outdoor Unit : CM1972Indoor Unit : KMS0972 × 3Power Supply : 230V Single Phase 60Hz< Cooling Capacity >5-2. Cooling CapacityTC : Total Co

Page 31 - 80°F (27°C

Outdoor Unit : CM2472Indoor Unit : KMS0972 × 3Power Supply : 230V Single Phase 60Hz< Cooling Capacity >TC : Total Cooling Capacity (BTU/h)

Page 32

Outdoor Unit : CM3172Indoor Unit : KMS0972 × 4Power Supply : 230V Single Phase 60Hz< Cooling Capacity >TC : Total Cooling Capacity (BTU/h)

Page 33

8FA2-5257-58800-1WHTREACTANCEWHTYELYELBLKBLKBLKBLK1111122112212 2223344COIL/OUTDOORYELYELYELYEL11223344A-THCOILTHERMISTORCOMPRESSORTHERMISTORAW THERMI

Page 34

APPLICABLE INDOOR UNITSCM1972CM2472CM3172Multi-Outdoor UnitIndoor Unit3-Room4-Room4-RoomKMS0772YESYESYESYESYESYESYESYESYESYESYESYESNOYESYESKMS0972

Page 35

8FA2-5257-59000-1WHTREACTANCEWHTYELYELBLKBLKBLKBLK1111122112212 2223344COIL/OUTDOORYELYELYELYEL11223344A-THCOILTHERMISTORCOMPRESSORTHERMISTORAW THERMI

Page 36 - 5-2. Cooling Capacity

8FA2-5257-89300-1WHTREACTANCEWHTYELYELBLKBLKBLKBLK1111122112212 2223344COIL/OUTDOORYELYELYELYEL11223344A-THCOILTHERMISTORCOMPRESSORTHERMISTORAW THERMI

Page 37 - < Cooling Capacity >

7. FUNCTIONS7-1. Explanation of FunctionsThe numerical values such as temperature, frequency, time and current in parentheses are an example of CM31

Page 38 - Indoor Unit : KMS0972 × 4

Control/conditionsCOOLThe ON/OFF operation button on the remote controller is pressed.The room temperature has reached the desired temperature.The out

Page 39 - 6. ELECTRICAL DATA

Control/conditionsSENSOR DRY(1/f fluctuation fan)The ON/OFF operation button on the remote controller is pressed.The outdoor unit does not operate for

Page 40 - Outdoor Unit CM2472

7-2. Protective FunctionsThe numerical values such as temperature, frequency, time and current in parentheses are an example of CM3172 and the values

Page 41 - Outdoor Unit CM3172

Current(A)Frequency (Hz)TripHz reductionHz increaseprohibitHz reductionHz increase prohibitHz reductionHz increase prohibit(16)(15.6)0(30)Example of o

Page 42 - 7. FUNCTIONS

8. TROUBLESHOOTING8-1. Precautions before Performing Inspection or RepairBoth the indoor unit and outdoor unit include electronic control circuits.

Page 43 - Frequency control

8-2. Trouble Diagnosis by Error Monitor LampsWARNINGTo prevent electric shock, do not inspect or repair until the Power Lamp on the P.C.Board is turn

Page 44 - 1/f fluctuation fan

8-3-1. Checking the outdoor unit8-3. Checking the Outdoor SystemWork procedureApply 220 V AC between terminals L1 and L2 on the outdoor unit termina

Page 45 - 7-2. Protective Functions

95 °F D.B. / 71 °F W.B.67 °F D.B. / 57 °F W.B.1. OPERATING RANGEMaximumMinimum115 °F D.B. 67 °F D.B.Temperature Indoor Air Intake Temp. Outdoor Air

Page 46 - 7-2-2. Low Start Current

8-4. Trouble Diagnosis of Each Part8-4-1. Problems of Each Part and Inspection PointsFor details about the inspection points, refer to the Inspectio

Page 47 - 8. TROUBLESHOOTING

8-4-2. Inspection Points for Each Part(1) Outdoor control circuit boardRefer to 8-3-1. Checking the outdoor unit.(2) FuseCheck it visually or the con

Page 48

No voltage on circuit board(6) Electric expansion valveWhen replacing the electric expansion valve and coil, be sure to attach the connectors in the c

Page 49

(7) Branch tubing temperature sensorCheck that the sensor is securely contained in the thermostat holder.(8) BreakerCheck whether or not the breaker h

Page 50

8-5. Trouble Diagnosis of Fan MotorThis outdoor DC fan motor contains an internal control PCB. Therefore, it is not possible to measure the coil resi

Page 51

9. REFRIGERANT R410A: SPECIAL PRECAUTIONS WHEN SERVICING UNIT9-1. Characteristics of New Refrigerant R410A9-1-1. What is New Refrigerant R410A?R410

Page 52

Tubing precautionsRefrigerant R410A is more easily affected by dust or moisture compared with R22, thus be sure to temporarily cover the ends of the t

Page 53

9-3. Tools Specifically for R410A For servicing, use the following tools for R410AGauge manifoldCharging hoseGas leak detectorRefrigerant cylinderCha

Page 54

9-5. In Case of Compressor Malfunction CAUTIONShould the compressor malfunction, be sure to make the switch to a replacement compressor as quickly as

Page 55 - 9. REFRIGERANT R410A:

ValveSingle valveCharge liquid refrigerant with cylinder in up-side-down position.Single valve (with siphon tube)Charge with cylinder in normal positi

Page 56

2. SPECIFICATIONS2-1. Unit SpecificationsOutdoor Unit CM1972Indoor Unit KMS0972 × 3Remarks:1. The values shown in performance section and electrica

Page 57

Length of tubingEvacuation timeLess than 33 ft. (10 m)More than 10 minutesMore than 33 ft. (10 m)More than 15 minutes9-6. In Case Refrigerant is Lea

Page 58

9-7. Charging Additional Refrigerant9-7-1. When Tubes are ExtendedObserve the proper amount of refrigerant as stated in this service manual or the i

Page 59

INSTALLATION INSTRUCTIONSCM1972CM2472CM3172(II-852-6-4190-214-00-3)APPENDIX AA-1

Page 60

85264190214003 © SANYO 2007ContentsPageIMPORTANT!Please Read Before Starting ... 21. GENERAL ...

Page 61 - 9-8-1. Use of Existing Units

2IMPORTANT! Please Read Before StartingThis air conditioning system meets strict safety and operatingstandards. As the installer or service person, it

Page 62 - APPENDIX A

31. GeneralThis booklet briefly outlines where and how to install theair conditioning system. Please read over the entire setof instructions for the

Page 63 - INSTALLATION INSTRUCTIONS

41-5. Additional Materials Required for Installation1. Refrigeration (armored) tape2. Insulated staples or clamps for connecting wire(See local codes

Page 64 - IMPORTANT!

5G Install the indoor unit more than 3.3' (1 m) away from anyantenna or power lines or connecting wires used for tele-vision, radio, telephone, s

Page 65 - 1. General

6(B)Fig. 4bUnion 1/2"(12.70mm)1/2"(12.70mm)Flare 3/8"(9.52mm)A joint for connecting tubes ofdifferent sizes(3/8"(9.52mm) 1/2&q

Page 66

7(B)Fig. 4dCBA(KMS0772,KMS0972,KMS1272)(KMS0772,KMS0972,KMS1272)DOutdoor unit Indoor unit(KMS0772,KMS0972,KMS1272)(KMS1872)1/2"(12.70mm)1/2"

Page 67

Outdoor Unit CM1972Indoor Unit KMS0972 × 3< 208V >Remarks:1. The values shown in performance section and electrical rating section above are ba

Page 68

8(A)Fig. 4gUnion 3/8"(9.52mm)Flare 1/2"(12.70mm)(1/2"(12.70mm) 3/8"(9.52mm)) Supplied ReducerCBA(KMS0772,KMS0972,KMS1272)(KMS0

Page 69

9(D)Fig. 4jUnion 5/8"(15.88mm)Flare 1/2"(12.70mm)(1/2"(12.70mm) 5/8"(15.88mm))Locally purchasedCBA(KMS0772,KMS0972,KMS1272)(KM

Page 70

2-3. Outdoor UnitAVOID:G heat sources, exhaust fans, etc. (Fig. 5a)G damp, humid or uneven locations.DO:G choose a place as cool as possible.G choose

Page 71

11(1) Recommended dimensions of the baffle platesDFECJHLIBKQRAGO(3- 6.5 mm) 3- 1/4"(2- 6 mm) 2- 15/64"ABHCEFKIJGGD(4- 6.5 m

Page 72 - About 16" (40 c

12(3) Installation procedurePanel topPanel frontPanel side RPanel side L1. Air Intake Baffle(1) Left side1. Remove the top panel from the unit.2. Remo

Page 73 - Air Discharge Baffle

13Fig. 6a23-15/165-11/3215/3235-7/16 (900)13-19/3212-19/3214-17/322-29/3229-1/8 (740)23/321-13/162-1/165-29/322-27/322-3/42-1/324-7/162-15/162-3/44-1/

Page 74

142-6. Diagram of Outdoor Unit InstallationNever install only a single indoor unit.Be sure to connect indoor and outdoor units only in combinations t

Page 75

153. Installation Process3-1. Embedding the Tubing and WiringG Do not connect tubes to locations that are embedded.G Be sure to bind refrigerant tub

Page 76 - Over 1'8"(50cm)

16When reaming, hold the tube end downward and be sure thatno copper scraps fall into the tube. (Fig. 9)(3) Remove the flare nut from the unit and be

Page 77 - Deburring

173-6. Insulation of Refrigerant TubingTo prevent heat loss and wet floors due to dripping of con-densation, both tubes must be well insulated with a

Page 78 - Service valve on

Outdoor Unit CM2472Indoor Unit KMS0972 × 3< 230V >Remarks:1. The values shown in performance section and electrical rating section above are ba

Page 79 - Apply putty here

184. Air PurgingAir and moisture remaining in the refrigerant system have undesirable effects as indicated below. Therefore, they must be purged comp

Page 80

19(4) With the “Lo” knob of the manifold valve open andhigh-pressure valve (“Hi”) closed completely, runthe vacuum pump. Run the pump until the pres-s

Page 81

20I Pump DownG When relocating or disposing of the A/C, request this service fromthe dealer where the unit was purchased, or from an appropriateagent.

Page 82 - Pump Down

215. Wiring Instructions5-1. General Precautions on Wiring(1) Before wiring, confirm the rated voltage of the unit asshown on its nameplate, then ca

Page 83 - 5. Wiring Instructions

22WARNINGG Be sure to comply with local codes on running thewire from the indoor unit to the outdoor unit (sizeof wire and wiring method, etc.).G Each

Page 84

23When connecting each power wire to the correspondingterminal, follow the instructions “How to connect wiringto the terminal” and fasten the wire sec

Page 85

24123123123123Indoor unit DIndoor unit BIndoor unit AIndoor unit CGroundPower: Single-phase, 230/208VAC 60HZPower switch(not provided)Outdoor unit ATe

Page 86

25Regulations on wire size differ from locality to locality. Forfield wiring requirements, please refer to your local electri-cal codes. Make sure tha

Page 87 - 6. Test Run

7. Connecting a Home Automation deviceThe HA (white) 4P terminal is located on the indoor unit PCB. If a HA device will be used, connect it to this t

Page 88 - 8. Installation Check Sheet

UNIT COMBINATION TABLESAPPENDIX BBe sure to operate the air conditioning system only when 2 or more indoor units have been installed. If operated with

Page 89

Outdoor Unit CM2472Indoor Unit KMS0972 × 3< 208V >Remarks:1. The values shown in performance section and electrical rating section above are ba

Page 90 - Conditions:

3-Room Outdoor Unit Combination TableSave this Combination Table!Please be sure to hand over this sheet to the user. Pub. OI-85264180818004 © SANYO 20

Page 91 - Voltage Rating : 230V 60Hz

NOTE< Combinations of operatable indoor units >CM1972(Rated cooling capacity at 230V: 19700 BTU/h)Voltage Rating : 230V 60Hz 7500 : KMS0772

Page 92 - Voltage Rating : 208V 60Hz

NOTECM1972(Rated cooling capacity at 208V: 19700 BTU/h)Voltage Rating : 208V 60Hz 7500 : KMS0772 9000 : KMS0972 11900 : KMS1272 17500 : KMS18

Page 93

Save this Combination Table!Please be sure to hand over this sheet to the user. Pub. OI-85264180819004 © SANYO 2008<Combinations of Connectable Ind

Page 94

NOTE< Combinations of operatable indoor units >CM2472(Rated cooling capacity at 230V: 25400 BTU/h)Voltage Rating : 230V 60Hz 7500 : KMS0772

Page 95

NOTECM2472(Rated cooling capacity at 208V: 24400 BTU/h)Voltage Rating : 208V 60Hz 7500 : KMS0772 9000 : KMS0972 11900 : KMS1272 17500 : KMS18

Page 96

Pub. OI-85264180820004 © SANYO 2008<Combinations of Connectable Indoor Units>The combinations of the indoor units listed in Table 1 and Table 2

Page 97

NOTE< Combinations of operatable indoor units >CM3172(Rated cooling capacity at 230V: 30600 BTU/h)-2-Voltage Rating : 230V 60Hz 7500 : KMS07

Page 98

NOTECM3172(Rated cooling capacity at 208V: 28600 BTU/h)Voltage Rating : 208V 60Hz 7500 : KMS0772 9000 : KMS0972 11900 : KMS1272 17500 : KMS18

Page 99

SANYO Commercial SolutionsA Division of SANYO North America Corporation1300 Michael Drive, Suite AWood Dale, IL 60191, U.S.A.Sanyo Canada Inc.1-300 Ap