1. Specifications
Indoor Unit: XH3642 Outdoor Unit: CH3642
• 230V / 1 phase / 60Hz
RATING CAPACITY : 34,500 BTU/h AIR FLOW RATE: 980 CFM
EVAPORATOR CONDENSER
ENT.TEMP.°F(°C) AMBIENT TEMP °F(°C)
WB DB 75 85 95 105 115
(23.9) (29.4) (35.0) (40.6) (46.1)
TC 34,950 33,260 31,330 29,150 26,740
CI 2.32 2.53 2.76 3.06 3.36
72(22.2) SHC 25,700 24,850 23,890 22,840 21,700
59 76(24.4) SHC 29,070 28,220 27,260 26,210 25,070
(15.0) 80(26.7) SHC 32,590 31,740 30,790 29,150 26,740
84(28.9) SHC 34,950 33,260 31,330 29,150 26,740
88(31.1) SHC 34,950 33,260 31,330 29,150 26,740
TC 36,260 34,640 32,910 30,950 28,810
CI 2.34 2.57 2.8 3.11 3.42
72(22.2) SHC 21,580 20,830 20,050 19,170 18,230
63 76(24.4) SHC 24,950 24,200 23,420 22,540 21,600
(17.2) 80(26.7) SHC 28,480 27,730 26,940 26,060 25,130
84(28.9) SHC 31,850 31,100 30,310 29,430 28,500
88(31.1) SHC 35,220 34,470 32,910 30,950 28,810
TC 37,640 36,160 # 34,500 32,670 30,670
CI 2.36 2.59 2.83 3.14 3.45
72(22.2) SHC 17,450 16,820 16,130 15,380 14,570
67 76(24.4) SHC 20,820 20,190 19,500 18,750 17,940
(19.4) 80(26.7) SHC 24,340 23,710 23,020 22,270 21,470
84(28.9) SHC 27,710 27,080 26,390 25,640 24,840
88(31.1) SHC 31,080 30,450 29,760 29,010 28,210
TC 39,640 38,260 36,780 35,160 33,360
CI 2.39 2.62 2.87 3.19 3.5
72(22.2) SHC 13,330 12,800 12,240 11,630 10,960
71 76(24.4) SHC 16,700 16,170 15,610 15,000 14,330
(21.7) 80(26.7) SHC 20,220 19,690 19,130 18,520 17,860
84(28.9) SHC 23,590 23,060 22,500 21,890 21,230
88(31.1) SHC 26,960 26,430 25,870 25,260 24,600
TC 40,430 39,120 37,740 36,160 34,470
CI 2.43 2.66 2.91 3.23 3.55
75 76(24.4) SHC 12,270 11,820 11,350 10,810 10,250
(23.9) 80(26.7) SHC 15,800 15,340 14,870 14,330 13,770
84(28.9) SHC 19,170 18,710 18,240 17,700 17,140
88(31.1) SHC 22,540 22,080 21,610 21,070 20,510
TC :Total Cooling Capacity (BTU/h)
SHC:Sensible Heat Capacity (BTU/h)
CI :Compressor Input (kW)
Rating conditions are
M.R.= 10.47 USpints/h
:Outdoor Ambient Temp.95° FDB
:Indoor Unit Entering Air Temp.80° FDB/67° FWB