8-3. Freeze Prevention (Cooling and Dry)
This function prevents freezing of the indoor heat exchange coil.
When the temperature of the indoor heat exchange coil falls below 2 °C for 2 minutes, the control circuit stops
the outdoor fan and compressor (The compressor stops 3 seconds after the outdoor fan stopped). During this
period, Indoor fan operates in LL. The outdoor fan does not start again until the temperature rises above 6°C.
(The compressor starts 2 seconds after the outdoor fan started.)
Outdoor fan
Compressor
Indoor fan
6°C
Indoor heat
exch. coil
temp.
2°C
ON
At least
approx. 2 min.
3 sec.
OFF
OFF
ON
ON
ON
Set Speed Set Speed
LL
2 sec.
41