4. COOLING CAPACITY
11
11
1 Indoor Unit: XS4232 Outdoor Unit: C4232, CL4232
• 208V / 1 phase / 60Hz
RATING CAPACITY : 40,500 BTU / h AIR FLOW RATE : 880 CFM
EVAPORATOR CONDENSER
ENT. TEMP. °F (°C) AMBIENT TEMP. °F (°C)
WB DB 75 85 95 105 115
(23.9) (29.4) (35.0) (40.6) (46.1)
TC 41,030 39,040 36,770 34,220 31,390
CI 2.97 3.24 3.53 3.95 4.37
72(22.2) SHC 27,990 26,830 25,550 24,150 22,650
59 76(24.4) SHC 30,830 29,680 28,400 27,000 25,500
(15.0) 80(26.7) SHC 33,810 32,650 31,370 29,980 28,480
84(28.9) SHC 36,660 35,500 34,220 32,820 31,320
88(31.1) SHC 39,500 38,350 36,770 34,220 31,390
TC 42,570 40,660 38,640 36,330 33,820
CI 3 3.29 3.58 4.01 4.44
72(22.2) SHC 24,210 23,190 22,140 20,970 19,730
63 76(24.4) SHC 27,050 26,030 24,980 23,810 22,580
(17.2) 80(26.7) SHC 30,030 29,010 27,960 26,790 25,560
84(28.9) SHC 32,880 31,860 30,810 29,640 28,400
88(31.1) SHC 35,720 34,710 33,650 32,480 31,250
TC 44,190 42,440 # 40,500 38,350 36,000
CI 3.02 3.31 3.62 4.05 4.48
72(22.2) SHC 20,400 19,550 18,620 17,620 16,560
67 76(24.4) SHC 23,250 22,390 21,470 20,470 19,400
(19.4) 80(26.7) SHC 26,220 25,370 24,450 23,450 22,380
84(28.9) SHC 29,070 28,220 27,290 26,290 25,230
88(31.1) SHC 31,920 31,060 30,140 29,140 28,070
TC 46,530 44,910 43,170 41,270 39,160
CI 3.06 3.35 3.67 4.11 4.55
72(22.2) SHC 16,690 15,970 15,210 14,400 13,510
71 76(24.4) SHC 19,530 18,810 18,050 17,240 16,360
(21.7) 80(26.7) SHC 22,510 21,790 21,030 20,220 19,340
84(28.9) SHC 25,360 24,640 23,880 23,070 22,180
88(31.1) SHC 28,200 27,480 26,720 25,910 25,030
TC 47,470 45,930 44,310 42,440 40,460
CI 3.11 3.4 3.73 4.17 4.61
75 76(24.4) SHC 15,330 14,720 14,090 13,370 12,620
(23.9) 80(26.7) SHC 18,310 17,700 17,060 16,340 15,600
84(28.9) SHC 21,160 20,540 19,910 19,190 18,450
88(31.1) SHC 24,000 23,390 22,760 22,040 21,290
TC : Total Cooling Capacity (BTU / h)
SHC : Sensible Heat Capacity (BTU / h)
CI : Compressor Input (kW)
Rating conditions are
: Outdoor Ambient Temp. 95 °F DB
: Indoor Unit Entering Air Temp. 80 °F DB / 67°F WB