SM830078
2. SPECIFICATIONS
(1) Unit Specifications
MODEL No. Indoor Unit TS4232
Outdoor Unit CL4232
POWER SOURCE 230 - 208 V / 1 Phase / 60 Hz
PERFORMANCE Cooling
Capacity BTU / h 42,000 40,500
kW 12.32 11.88
Air circulation (Hi)
cu.ft. / min.
900 800
Moisture removal (High) Pints / h 14.8 14.6
ELECTRICAL RATINGS
Voltage rating VAC 230 208
Available voltage range VAC 187 - 253
Running amperes* A 20.6 21.0
Max. running amperes** A 21.4 22.7
Power input W 4,190 4,100
Power factor % 88 94
S.E.E.R
BTU / Wh
10.2 10.3
Max. starting amperes A 134 134
Maximum fuse size A 50
FEATURES
Controls Microprocessor
Low ambient control Built-in 0 °F
Timer ON / OFF 24-hours & Program
Fan speed Indoor / Outdoor 3 and Automatic control / 3 (Auto)
Air deflection Horizontal / Vertical Manual / Automatic
Air filter Washable, easy access, long life (2,500 hr)
Remote controller (Accessory) RCS - 5PS4U
Refrigerant control Capillary tube
Refrigerant tubing connections Flare type
Drain pipe trade size 3 / 4 in. (26.7 mm)
Compressor Scroll
Operation sound Indoor - Hi / Me / Lo dB - A 42 / 40 / 35
Outdoor - Hi dB - A 56
REFRIGERANT TUBING
Limit of tubing length ft. (m) 165 (50)
Limit of tubing length at shipment ft. (m) 50 (15)
Limit of elevation difference ft. (m) Outdoor unit is higher than indoor unit: 165 (50)
between the two units Outdoor unit is lower than indoor unit: 100 (30)
Refrigerant tube Narrow tube in. (mm) 3 / 8 (9.52)
outer diameter Wide tube in. (mm) 3 / 4 (19.05)
Refrigerant amount at shipment lbs. (kg) R22 : 9.7 (4.4)
DIMENSIONS & WEIGHT Indoor unit Outdoor unit
Unit dimensions Height in. (mm) 9-7/16 (240) 48-5/8 (1,235)
Width in. (mm) 62 (1,575) 37 (940)
Depth in. (mm) 26-3/8 (670) 13-3/8 (340)
Package dimensions Height in. (mm) 12-15/32 (317) 52-7/32 (1,326)
Width in. (mm) 66-1/16 (1,678) 40 (1,016)
Depth in. (mm) 31-1/16 (789) 16-3/8 (416)
Net weight lbs. (kg) 84 (38) 205 (93)
Shipping weight lbs. (kg) 97 (44) 229 (104)
Shipping volume cu.ft. (m
3
) 14.8 (0.42) 19.8 (0.56)
DATA SUBJECT TO CHANGE WITHOUT NOTICE
Cooling :
Rating conditions (*) : Indoor air temperature 80 °F DB / 67 °F WB, Outdoor air temperature 95 °F DB / 75 °F WB
Full load conditions (**) : Indoor air temperature 80 °F DB / 67 °F WB, Outdoor air temperature 115 °F DB