ENVIRONMENTALLY FRIENDLY TECHNOLOGY SUPER ABSORPTION
SANYO control system
Display and control board
Display(normal)
Table 1. Indication lamp Sample 1.
Sample 2.
Exhaust gas temp 236°C
CH W temp 12.3 7.1°C
Notice : Low level vacuum
Caution : Foul tube of COW
Name Lamp color
Running(Operation) indication lamp Red
Stop indication lamp Green
Alarm indication lamp Orange
Bunner combustion indication lamp Red
Cooling / Heating indication lamp Orange
Remote / Local select button with lamp Red
Mode select button with lamp Red
Data display LCD
symbol
Table 2. Typical operation data
High temperature generator
Exhaust gas
Chilled water
Cooling water
Hot water
Chiller / heater
Combustion
No.1 Absorbent pump
Refrigerant pump
Low level vacuum (Notice / Caution)
High concentration (Notice / Caution)
Foul tube of cooling water (Notice / Caution)
High cooling water temperature (Notice / Caution)
Foul chamber (Notice / Caution) (only for oil-fired types)
Chilled water
Hot water
Chiller / heater
Burner
Temperature
Operation hours
Message
Set point
ON-OFF
Table 3. Typical alarm data
Operation alarm
Others
Generator solution level
Thermal relay of No.1 Absorbent pump
Thermal relay of No.2 Absorbent pump
Thermal relay of burner blower
Thermal relay of oil pump
Thermal relay of refrigerant pump
Interlock of chilled water pump
Interlock of hot water pump
Interlock of cooling water pump
Interlock of system
Generator pressure
Chilled water flow rate
Hot water flow rate
Generator temperature
High concentration
Purge tank pressure sensor
Solution temp sensor
Condensed refrigerant temp sensor
Generator temp sensor
Chilled water sensor
Hot water sensor
Cooling water sensor
Refrigerant temp sensor
Power failure
The SANYO control system surpasses other proportional only control
systems available today. The digital PID(proportional, integral, and dif-
ferential) control maximizes unit performance by maintaining a ±0.5°C
deviation in leaving chilled water temperature from setpoint. Proportional
controls typically can only maintain a ±1°C deviation from setpoint. The
controller's innovative design also incorporates the ability to start and
stop the system chilled/hot and cooling water pumps. During shutdown
these pumps are sequenced to insure a complete dilution cycle.
The leaving chilled water temperature is measured every five seconds
and fuel input is changed according to the gradient of the leaving chilled
water temperature curve. System temperatures, setpoints, and opera-
tional records are displayed along with indicator lights for the chiller, pumps
and burner.
The SANYO control system offers its users self-diagnostics by constantly
monitoring the chiller's status and will automatically shut the chiller down
should a fault occur. The cause of shutdown will be retained in memory
and can be displayed for immediate operator review. The controller's
memory will also retain and display the cause of the last three system
fault conditions. This method of retaining fault conditions is extremely
useful for maintaining an accurate record of unit performance and fault
history.
MODE
SETTING
STOP RUN
CHILLER
BUZZER STOP
STOP LOCAL
REMOTE
OPERATION
ALARM
BURNER
HEATING
COOLING
REF PUMP
#1 ABS PUMP
#2 ABS PUMP
PURGE PUMP
BURNER BLOWER
H Generator temp 149.9°C