Sanyo DE User Manual Page 6

  • Download
  • Add to my manuals
  • Print
  • Page
    / 50
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 5
8
9
ENVIRONMENTALLY FRIENDLY TECHNOLOGY SUPER ABSORPTION
Optimum dilution cycle period can be shortened substantially according to microprocessor monitoring
This results in the appropriate dilution cycle operating hours.
Graph 6. Dilution cycle (DE)
Purge system
The high performance purge system maintains the required operating
pressure, preserves the chiller performance characteristics, minimizes
chiller maintenance as one purge time operation per season in case there
are four(4) seasons.
05
78
10 15 20
20
40
60
80
100
120
140
25 30 35 40
0
7°C
10
20
30
40
Temperature (°C)
Setting
Variable
(
5-30minutes
)
15minutes
ex.
Steam consumption
Cooling water inlet temperature
Chilled water inlet temperature
Chilled water outlet temperature
Steam control valve
opening ratio
Steam Consumption ratio (%)
Steam control opening ratio (%)
30minutes
Time
(
minutes
)
Steam valve opening control
Operation
signal
ON
OFF
Chiller /
heater
ON
OFF
Cooling water
pump
ON
OFF
Chilled / hot
water pump
ON
OFF
1 min T 1 1 min T 2
Stop signal Chiller stop
T1: Count the time until generator temperature goes down to 120°C
(About 4 to 20 minutes)
T2: Decide the time by generator temperature.
(About 5 to 10 minutes)
Note :
1) Dilution time in cooling operation is minimum 6 minutes
to maximum 15 minutes.
2) Dilution time in heating operation is 5 minutes.
Unit proper and hot water pump stop in 5 minutes after stop signal is lit.
3) Stop the air conditioning system after complete stop of chiller.
Graph 7. Start up chart (NE)
Open angle of steam control valve at starting is controlled
by means of the three steps, resulting that the excessive
amount of steam and also the consumed time to reach the
desired level became less than the previous model.
Of course, by means of adjusting the open speed of steam
control valve at the second step and the third, it is possible
to set up to the most suitable condition met to the site aux-
iliary equipment.
ON
OFF
16
12
8
4
0
0 5 10 15 20 25 30 35 40
Time(minutes)
Continuous operation of E model absorbent pump
Load factor 80% Load factor 40%
Conventional
Conventional
Load change
Chilled water inlet temperature
Chilled water outlet temperature
E model
E model
Absorbent
pump
Conventional pump
ON-OFF(3 times)
Temperature
(°C)
Temperature
setting 7°C
100
80
60
40
20
0
20 40 60 80 100
Cooling load factor(%)
Non-inverter
control
E model
Fuel consumption ratio(%)
Load factor(%)
100
50
30
Temperature(°C)
32
27
25
1. Chilled water outlet temperature 7°C constant
2. Cooling water inlet temperature
Speedy digital PID control
The introduction of new digital PID control to the E-model stabilizes the
chilled/hot water temperature with high accuracy than the previous C
model. It quickly responds to the load fluctuation and supplies stable
Control of high temperature generator by solution level control
With the new control system, solution flow rate is precisely controlled so
that the solution level of the high temperature generator is maintained at
a certain level.
Frequency of maneuvering has been substantially reduced with the syner-
Saving energy with the inverter
Balancing the load and flow rate with the absorbent pumps inverter con-
trol enables efficient and energy saving operation. As a result, it saves
the
input energy and electric power consumption, running cost by 5%
compared to none-inverter control.
chilled/hot water temperature. It is suitable for air-conditioning intelligent
buildings which require sophisticated control.
getic
effect of absorbent pump inverter control. This enables the supply
of a more
stable temperature for chilled/hot water compared to conven-
tional
models.
Graph 4. Operating result by speedy PID control (gas-fired)
Graph 5. Running cost curve Table 4. Test condition
Page view 5
1 2 3 4 5 6 7 8 9 10 11 ... 49 50

Comments to this Manuals

No comments