TECHNICAL & SERVICE MANUALKS1872 + C1872 + CL1872KS2472 + C2472 + CL2472DC INVERTER SPLIT SYSTEM AIR CONDITIONERIndoor UnitOutdoor Model N
Indoor Unit KS1872Outdoor Unit CL1872< 230V >DATA SUBJECT TO CHANGE WITHOUT NOTICE.Remarks: Rating conditions are:Cooling: Indoor air temperatur
113-4. Remove the Grille to Install the Indoor UnitBasically, these models can be installed and wired with-out removing the grille. If access to any
123-5. Shape the Indoor Side Tubing(1) Arrangement of tubing by directiona) Right or left tubingCut out the corner of the right/left frame with ahack
13(A)+(B) (A) Power Supply Wiring Length (ft) (C) ControlFuse or Circuit AWG(B) Power Line Length (ft) Line Length (ft)Model (#14) (#12) (#14)Breaker
143-8. Wiring Instructions for Inter-unit Connections(1) Insert the inter-unit wiring (according to local codes)into the through-the-wall PVC pipe. R
15When connecting each power wire to the correspondingterminal, follow the instructions “How to connect wiringto the terminal” and fasten the wire sec
163-9. Mounting(1) To install the indoor unit, mount the indoor unit ontothe 2 tabs on the upper part of the rear plate. (2) Hold down the air discha
17Hole in wallBent partNarrow tubeWide tubeRear panelFig. 38Drain capDrain hoseFig. 39I Left-side tubing(1) Lead the tubing and drain hose through the
18To unmount indoor unitPress the 2 LL marks on the lower part of the indoor unitand unlatch the tabs. Then lift the indoor unit andunmount. (Fig. 42)
194. How to Install the Outdoor UnitFirst refer to Section 2. Installation Site Selection.4-1. Wiring Instructions for the Outdoor UnitRegulations o
205. Refrigerant Tubing5-1. Use of the Flaring MethodMany of the conventional split system air conditionersemploy the flaring method to connect refr
Indoor Unit KS1872Outdoor Unit CL1872< 208V >DATA SUBJECT TO CHANGE WITHOUT NOTICE.Remarks: Rating conditions are:Cooling: Indoor air temperatur
215-4. Connecting Tubing between Indoor and Outdoor Unitsa) Tightly connect the indoor side refrigerant tubing exten-ded from the wall with the outdoo
226. Air PurgingAir and moisture remaining in the refrigerant systemhave undesirable effects as indicated below. Therefore,they must be purged comple
23(5) With the vacuum pump still running, close the “Lo”knob of the manifold valve. Then stop the vacuumpump.(6) With the accessory hex wrench, turn t
24How to Test Run the Air ConditionerAfter turning on power to the air conditioner, use the remotecontroller and follow the steps below to conduct the
25I Pump DownPump down means collecting all refrigerant gas in thesystem back into the outdoor unit without losing any ofthe gas. Pump down is used wh
267. Remote Control Unit Installation PositionThe remote control unit can be operated from either anon-fixed position or a wall-mounted position.To e
278. Address Switch8-1. Address Setting of the Remote Control UnitThe address can be set in order to prevent interferencebetween remote controllers
SANYO Commercial SolutionsA Division of SANYO North America Corporation1300 Michael Drive, Suite AWood Dale, IL 60191, U.S.A.Sanyo Canada Inc.1-300 Ap
Indoor Unit KS2472Outdoor Unit CL2472< 230V >DATA SUBJECT TO CHANGE WITHOUT NOTICE.Remarks: Rating conditions are:Cooling: Indoor air temperatur
Indoor Unit KS2472Outdoor Unit CL2472< 208V >DATA SUBJECT TO CHANGE WITHOUT NOTICE.Remarks: Rating conditions are:Cooling: Indoor air temperatur
Indoor Unit KS1872MP24Z3Flap MotorType Stepping MotorRating ModelCoil Resistance Ohm(Ambient Temp. 77 °F (25 °C))Each Pair of Terminal : 400 +/- 7%DC
Indoor Unit KS2472MP24Z3Flap MotorType Stepping MotorRating ModelCoil Resistance Ohm(Ambient Temp. 77 °F (25 °C))Each Pair of Terminal : 400 +/- 7%DC
Outdoor Unit C18722-2-2. Outdoor UnitControl PCBControl Circuit Fuse ControlsPart No.Microprocessor250V 25ACB-C1872DATA SUBJECT TO CHANGE WITHOUT NOT
Outdoor Unit C2472Control PCBControl Circuit Fuse ControlsPart No.Microprocessor250V 25ACB-C2472DATA SUBJECT TO CHANGE WITHOUT NOTICE.Pints (cc) - Mic
Outdoor Unit CL1872Control PCBControl Circuit Fuse ControlsPart No.Microprocessor250V 25ACB-CL1872DATA SUBJECT TO CHANGE WITHOUT NOTICE.Pints (cc) WHT
Outdoor Unit CL2472Control PCBControl Circuit Fuse ControlsPart No.Microprocessor250V 25ACB-CL2472DATA SUBJECT TO CHANGE WITHOUT NOTICE.Pints (cc) - M
When WiringELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM.SP
2-3. Other Component Specifications Indoor Unit KS1872 KS2472Outdoor Unit C1872 C2472 CL1872 CL2472032 50 68 86 104 122 140 158 176 194(0) (10)
3. DIMENSIONAL DATAIndoor Unit KS1872 KS2472Unit: inch(mm)21
Unit: inch(mm)Narrow tube service valvedia.1/4" (6.35)Wide tube service valvedia.1/2" (12.70)4-3/8 2-5/326-17/325-23/323/3226-3/8 (670)23/32
Wide tube service valvedia.5/8" (15.88)Narrow tube service valvedia.1/4" (6.35)4-7/165-29/322-1/32 4-1/229-1/8 (740)23/321-21/3235-7/16(900)
CompressorAccumulatorWide tubeservicevalveWide tubeNarrowtubeservicevalveNarrow tubeHeat exchangerHeat exchangerMufflerCooling cycleIndoor unit Outdoo
5. PERFORMANCE DATA5-1. Temperature ChartsIndoor Unit KS1872Outdoor Unit C1872• Check each performance value in test-run mode. Electrical performa
Indoor Unit KS1872Outdoor Unit CL1872• Check each performance value in test-run mode. Electrical performance values represent a combined indoor/ou
Indoor Unit KS2472Outdoor Unit C2472Cooling Characteristics (RH : 46%, Indoor fan speed : High fan) (60Hz, 230V)(1) Low pressure performance chart
Indoor Unit KS2472Outdoor Unit CL2472Cooling Characteristics (RH : 46%, Indoor fan speed : High fan) (60Hz, 230V)(1) Low pressure performance char
Indoor Unit : KS1872Outdoor Unit : C1872 / CL1872Power Supply : 230V Single Phase 60Hz< Cooling Capacity >5-2. Cooling CapacityTC : Total
Table of Contents1. OPERATING RANGE2. SPECIFICATIONS2-1. Unit Specifications 2-2. Major Component Specifications 2-3. Other Component Specifica
Indoor Unit : KS2472Outdoor Unit : C2472 / CL2472Power Supply : 230V Single Phase 60Hz< Cooling Capacity >TC : Total Cooling Capacity (BTU
Indoor Unit : KS1872Outdoor Unit : CL1872Power Supply : 230V Single Phase 60Hz< Cooling Capacity (Low Ambient) >5-3. Cooling Capacity (Lo
Indoor Unit : KS2472Outdoor Unit : CL2472Power Supply : 230V Single Phase 60Hz< Cooling Capacity (Low Ambient) >TC : Total Cooling Capacit
Horizontal distance (ft.)Axis air velocity (ft./sec.)Vertical distance (ft.)Room air temp. : 80°F (26.7°C)Fan speed : HighCooling : Flap angle 0 , :
Horizontal distance (ft.)Axis air velocity (ft./sec.)Vertical distance (ft.)Room air temp. :80°F (26.7°C)Fan speed : HighCooling : Flap angle 0 , :
6. ELECTRICAL DATA6-1. Electrical CharacteristicsIndoor UnitKS1872Outdoor UnitC1872Indoor Unit Outdoor UnitFan Motor Fan Motor + CompressorPerform
Indoor UnitKS2472Outdoor UnitC2472Indoor Unit Outdoor UnitFan Motor Fan Motor + CompressorPerformance at 230V Single-phase 60HzRating conditions R
EVAPORATORTERMINAL BASETO OUTDOOR UNITGRN/YELLAMP10P(WHT)FLAP5P (WHT)FLAPCONNECTORFLAP MOTORREDPNKBLUBRNYEL12345123451234512345AC1 AC2 SIWHTREDWHTWHTW
8FA2-5257-68600-3REACTANCENLGND123456POWERSUPPLY3211 2 3CMCOMPRESSORMOTORRED (PNK)WHTBLURED(PNK)WHTBLUFERRITECORE3P-CONNECTOR (WHT)RSTW WWWWCONTROLLER
NLGND123456POWERSUPPLYTERMINALPLATEFERRITECOREGNDTO INDOOR UNITPOWER RELAY6145BLKBLKWHTBLKBLK2P-CONNECTOR (BLK)HIGH PRESSURESWITCH1 12 2WHTWACIN1WACIN
11. REFRIGERANT R410A: SPECIAL PRECAUTIONS WHEN SERVICING UNIT11-1. Characteristics of New Refrigerant R410A11-2. Checklist before Servicing11-3. T
NLGND123456POWERSUPPLYTERMINALPLATEFERRITECOREGNDTO INDOOR UNITPOWER RELAY6145BLKBLKWHTBLKBLK2P-CONNECTOR (BLK)HIGH PRESSURESWITCH1 12 2WHTWACIN1WACIN
1HR.TIMERbuttonON/OFFoperationbutton ACL(Reset)buttonIONbutton7. MAINTENANCE7-1. Address Setting of the Remote Control UnitThe address can be set in
One of the two types of connectors illustrated at left is used. Theirbasic structure is the same for each. How to DisconnectHold the resin connector c
Emergency operation SENSOR DRY During DRY operation, the system adjusts the room temperature and fan speed according to the conditions in the room, i
HIGH POWERNIGHT SETBACKLamp colorsTimer backupThis function acts to raise the power but keeps the AC system in the same operating mode.This function i
Compressor discharge temperature controlFreeze preventionDuring COOL or DRY operation, freezing is detected and operation is stopped when the temperat
1HR.TIMERbuttonON/OFFoperationbutton ACL(Reset)buttonIONbutton< Clock display >Test run modeSelf-diagnostics mode9. TROUBLESHOOTING9-1. Precau
Since the indications cover various units, the corresponding parts listed below may not be present in some models.REMOTE CONTROL receiver(1) OPERAT
(2) If the self-diagnostics function fails to operateCheck the indoor unit.Is the fuse blown?Replace the controller.Replace the circuitboard or the fu
9-3. Checking the Indoor and Outdoor Units(1) Checking the indoor unit(2) Checking the outdoor unit Using the TEST/T-RUN terminalsControlNo. Check ite
95 °F D.B. / 71 °F W.B.67 °F D.B. / 57 °F W.B.1. OPERATING RANGEMaximumMinimum115 °F D.B.67 °F D.B.Temperature Indoor Air Intake Temp. Outdoor Air In
(3) Serial Communication Error Identification ProcedureRefer to "Method of Self-Diagnostics" for the self-diagnostics procedure.(3-1) Condit
What is the latest self-diagnosis result ?Condition: E12Defect in the outdoor unitP. C. board.Condition: E01Defect or connection errorin the inter-uni
(3-2) Condition: E12Troubleshooting Serial Communication1. Turn off the power and wait until the power lamp (LED) of the outdoor unit controller is
[Trouble symptom 3] Motor rotates for some time (several seconds), but then quickly stops, when the indoor unit operates.(There is trouble in the sys
9-4-2. Outdoor Fan MotorThis outdoor DC fan motor contains an internal control PCB. Therefore, it is not possible to measure the coil resistance, and
9-5. Noise Malfunction and Electromagnetic InterferenceAn inverter A/C operates using pulse signal control and high frequencies. Therefore, it is sus
Insulation testerProbeClipGround wireTerminal plateCoppertube ormetallic partClipInsulation testerProbeFig. 1Fig. 2Fig. 3Fig. 4Coppertube ormetallic p
FusePCB Ass'yFig. 5Fig. 6Fuse10-2. Checking Continuity of Fuse on PCB Ass'yRemove the PCB Ass'y from the electrical component box. The
11. REFRIGERANT R410A: SPECIAL PRECAUTIONS WHEN SERVICING UNIT11-1. Characteristics of New Refrigerant R410A11-1-1. What is New Refrigerant R410A?R
Tubing precautionsRefrigerant R410A is more easily affected by dust or moisture compared with R22, thus be sure to temporarily cover the ends of the t
2. SPECIFICATIONS2-1. Unit SpecificationsIndoor Unit KS1872Outdoor Unit C1872< 230V >DATA SUBJECT TO CHANGE WITHOUT NOTICE.Remarks: Rating con
11-3. Tools Specifically for R410A For servicing, use the following tools for R410AGauge manifoldCharging hoseGas leak detectorRefrigerant cylinderCh
11-5. In Case of Compressor Malfunction CAUTIONShould the compressor malfunction, be sure to make the switch to a replacement compressor as quickly a
ValveSingle valveCharge liquid refrigerant with cylinder in up-side-down position.Single valve (with siphon tube)Charge with cylinder in normal positi
Length of tubingEvacuation timeLess than 33 ft. (10 m)More than 10 minutesMore than 33 ft. (10 m)More than 15 minutes11-6. In Case Refrigerant is Le
11-7. Charging Additional Refrigerant11-7-1. When Tubes are ExtendedObserve the proper amount of refrigerant as stated in this service manual or the
INSTRUCTION MANUALKS1872 + C1872 + CL1872KS2472 + C2472 + CL2472(OI-852-6-4180-800-00-2)APPENDIX AA-1
2FeaturesThis air conditioner is an inverter type unit that automatically adjusts capacity as appropriate. Details on these functions are provided bel
3ContentsPageFeatures... 2Product Information
4Installation Location• We recommend that this air conditioner be installed properly by qualified installation technicians in accordance with the Inst
5Names of PartsThis illustration is based on the external view of a standard model.Consequently, the shape may differ from that of the air conditioner
Indoor Unit KS1872Outdoor Unit C1872< 208V >DATA SUBJECT TO CHANGE WITHOUT NOTICE.Remarks: Rating conditions are:Cooling: Indoor air temperature
6Unit Display and Operation ButtonREMOTE CONTROL receiver This section picks up infrared signals from the remote control unit (transmitter).OPERATION
7Remote Control Unit (Display)(1) Operation modeMILD DRY ...COOL...FAN ...
8Remote Control UnitThe illustration above pictures the remote control unit after the cover has been opened.Transmitter When you press the buttons on
9Remote Control Unit (continued)Temperature setting buttons(TEMP.)Press the button to increase the set temperature.Press the button to reduce the
10Remote Control Unit (continued)Using the Remote Control UnitSENSOR button When you press this button (use a small-tipped object such as a ballpoint
11Using the Remote Control Unit (continued)How to Use the RemoteControl UnitWhen using the remote control unit, always point the unit’s transmitter he
12Operation with the Remote Control Unit 1. OperationCheck that the circuit breaker on the power panel is turned on.Press the setting buttons as desc
13Operation with the Remote Control Unit (continued)• Choose the best position in the room for the remote control unit, which also acts as the sensor
14Operation with the Remote Control Unit (continued)4. Night Setback ModeNight Setback Mode is used for saving energy.Press the NIGHT SETBACK button
15Operation with the Remote Control Unit (continued) 5. QUIET ModeQUIET Mode is used to reduce the fan sound of the indoor unit. Press the QU
Indoor Unit KS2472Outdoor Unit C2472< 230V >DATA SUBJECT TO CHANGE WITHOUT NOTICE.Remarks: Rating conditions are:Cooling: Indoor air temperature
16Special RemarksHow it works? • Once the room temperature reaches the level that was set, the unit’s operation frequency is changed automatically.• D
17Setting the Timer In the descriptions below, the following settings are used for the temperature and time indicator selector button on the bottom f
18Setting the Timer (continued)3. How to set the ON time(Example) To start operation at 7:10 am.4. How to set DAILY ON/OFF REPEAT timer(Example) To st
19Using the 1-Hour OFF TimerTips for Energy Saving1. 1-Hour OFF Timer This function causes the unit to operate for one hour and then stop, regardless
20Adjusting the Airflow Direction1. Horizontal The horizontal airflow can be adjusted by moving the vertical vanes with your hands to the left or righ
21Operation without the Remote Control UnitCare and CleaningINDOOR UNIT If you have lost the remote control unit or it has trouble, follow the steps b
22Care and Cleaning (continued)Anti-Mold Filter The anti-mold filter behind the air intake grille should be checked and cleaned at least once every tw
23Care and Cleaning (continued)Air Clean Filter The air clean filter removes dust and dirt from the air, and reduces odors and smoke from tobacco.This
24TroubleshootingIf your air conditioner does not work properly, first check the following points before requesting service. If it still does not work
INSTALLATION INSTRCTIONSKS1872 + C1872 + CL1872KS2472 + C2472 + CL2472(II-852-6-4189-988-00-3)APPENDIX BA-2
Indoor Unit KS2472Outdoor Unit C2472< 208V >DATA SUBJECT TO CHANGE WITHOUT NOTICE.Remarks: Rating conditions are:Cooling: Indoor air temperature
85264189988003 © SANYO 2007ContentsPageIMPORTANT!Please Read Before Starting ... 21. GENERAL ...
2IMPORTANT! Please Read Before StartingThis air conditioning system meets strict safety and operatingstandards. As the installer or service person, it
31. GeneralThis booklet briefly outlines where and how to install theair conditioning system. Please read over the entire setof instructions for the
41-5. Additional Materials Required for Installation1. Refrigeration (armored) tape2. Insulated staples or clamps for connecting wire(See local codes
52-2. Outdoor UnitAVOID:G heat sources, exhaust fans, etc. (Fig. 4)G damp, humid or uneven locations.DO:G choose a place as cool as possible.G choose
62-3. Baffle Plate for the Outdoor Unit(CLxx models only)It is recommended to use baffle plates for modelsCL1872 and CL2472. The baffle plates are no
7(1) Recommended dimensions of the baffle platesDFECJHLIBKQRAGO(3- 6.5 mm) 3- 1/4"(2- 6 mm)2- 15/64"ABHCEFKIJGGD(4- 6.5 mm)
8(3) Installation procedurePanel topPanel frontPanel side RPanel side LFig. 5j1. Air Intake Baffle(1) Left side1. Remove the top panel from the unit.2
9Set screw only for transportationFig. 6Rear panelmarksFig. 7Left tubingRight tubingDownward tubingRight-rear tubing(recommended)Left-rear tubingFig.
10IndoorsideOutdoorsideHole should be made at a slight downward slant to theoutdoor side.NOTEFig. 10Plastic coverINSIDE OUTSIDEWallSlightanglePVC pipe
Comments to this Manuals