7. INSTALLATION INSTRUCTIONS
7-1. Installation Site Selection
7-1-1. Indoor Unit
AVOID:
direct sunlight.
nearby heat sources that may affect performance of
the unit.
areas where leakage of flammable gas may be
expected.
places where large amounts of oil mist exist.
DO:
select an appropriate position from which every cor-
ner of the room can be uniformly cooled. (High on a
wall is best.)
select a location that will hold the weight of the unit.
select a location where tubing and drain hose have
the shortest run to the outside. (Fig. 1)
allow room for operation and maintenance as well as
unrestricted air flow around the unit. (Fig. 2)
install the unit within the maximum elevation differ-
ence (H) above or below the outdoor unit and within
a total tubing length (L) from the outdoor unit as
detailed in Table 1 and Fig. 3.
Install the indoor unit more than 1 meter away from any
antenna or power lines or connecting wires used for
television, radio, telephone, security system, or inter-
com. Electrical noise from any of these sources may
affect operation.
Table 1
5 cm
min.
5 cm
min.
15 cm min.
Front View
Fig. 1
INDOOR
UNIT
Tubing length (L)
OUTDOOR
UNIT
Elevation
difference (H)
Fig. 2
WARNING
To prevent abnormal heat
generation and the possibility
of fire, do not place obstacles,
enclosures and grilles in front
of or surrounding the air con-
ditioner in a way that may
block air flow.
Indoor unit
Floor level
Wall
Minimum height
from floor level
1.5 m
Fig. 3
For stable operation of
the air conditioner, do not
install wall-mounted type
indoor units less than
1.5 m from floor level.
CAUTION
Max. Allowable Tubing Limit of Tubing Limit of Elevation Required Amount of
Model Length at Shipment Length (L) Difference (H) Additional Refrigerant
(m) (m) (m) (g/m)
*
KRV93 / 123 7.5 15 7 15
*
If total tubing length becomes 7.5 to 15 m (max.), charge additional refrigerant (R410A) by 15 g/m.
No additional compressor oil is necessary.