Sanyo CG1411 User Manual Page 35

  • Download
  • Add to my manuals
  • Print
  • Page
    / 100
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 34
31
8-2. Cooling
8-2-1. Room Temperature Control
Room temperature control is obtained by cycling the compressor ON and OFF under control of the room
temperature sensor in the indoor unit.
All information is transmitted every 3 minutes by the remote control unit to the controller in the indoor unit.
The control circuit will not attempt to turn the compressor ON until the compressor has been OFF for at
least 3 minutes. To protect the compressor from stalling out when trying to start against the high side
refrigerant pressure, the control circuit has a built-in automatic time delay to allow the internal pressure to
equalize.
As a protective measure, the control circuit switches the compressor OFF after 3 minutes or more of com-
pressor operation.
Thermo. ON: When the room temperature is above T°F (T°F is set temperature).
Compressor ON
Thermo. OFF: When the room temperature is equal to or below set temperature T – 1°F.
Compressor OFF
3 minutes 3 minutes 3 minutes
Set temp.
T°F
T – 1°F
Compressor
More than
3 minutes
Set speed
OFF OFF
OFF OFF
Outdoor fan
Indoor fan
Thermo.
OFF
Thermo.
ON
Thermo.
OFF
Thermo.
ON
Page view 34
1 2 ... 30 31 32 33 34 35 36 37 38 39 40 ... 99 100

Comments to this Manuals

No comments