8-3-4. Cold Draft Prevention Function (During Heating Operation)
This function prevents a cold draft from being released at the beginning of Heating Operation or during operation
of the room temperature thermo.
Change in Fan Speed
● When Heating Operation is started with the temperature of the heat exchanger less than 90°F (32°C):
● Until the temperature of the heat exchanger goes over 117°F (47°C), fan speed varies according to the
temperature of the heat exchanger.
● Once the temperature of the heat exchanger rises over 117°F (47°C), cold draft prevention function is
released.