11. POINTS TO DIAGNOSE
11-1. Indoor Unit Alarm Signal
11-2. Manifold Pressure
To set manifold pressure there are 2 settings – low pressure and high pressure.
Use SW1 to move to the 2 modes used to adjust the two pressures.
Press SW1 1 time for low pressure.
Press SW1 2 times for high pressure.
Press SW1 3 times for normal operation.
Use VR1 to set the low, lighting pressure and VR2 to set the high pressure.
Step 1: Set low pressure
1. Press SW1 and hold until LEDs 4 and 5 flash.
2. Adjust the low pressure with VR1 to 0.63 inches of water column.
Step 2: Set high pressure
1. Press SW1 again and LEDs 1 and 2 will flash.
2. Adjust pressure with VR2 to 3.43 inches of water column.
Step 3: Set lighting pressure
Lighting pressure will be set automatically from Step 1 and Step 2.
Check these settings 2 or 3 times to insure all are correct then reset until no LEDs flash.
NOTE
Alarm Signal Error Meaning Operation Information
Misconnection of inter-unit wiring Heating • Cooling • Dry Connect correctly
Room temp. thermistor is defective Heating • Cooling • Dry Normal: 9 – 11 kat 50°F
4 – 6 kat 77°F
Power Lamp Heat exch. thermistor is defective Heating • Cooling • Dry Normal: 100 – 120 k at 50°F
Flashing 50 – 60 kat 77°F
Fan motor is defective Heating • Cooling • Dry Alarm signal appears in 1 min.
Amp. current is high Heating • Cooling • Dry More than 17 amp.
Amp. current is low Heating • Cooling • Dry Less than 0.8 amp.
Heat exch. thermistor detects high temp Heating More than 154°F (68°C)
Outdoor Unit Fuel Inlet Pressure W.C. (kPa) Manifold Pressure W.C. (kPa)
Low High Lighting (10 sec.)
LD4, 5 Flashing LD2, 3 Flashing (verification)
CG1411 Natural gas 7.0 (1.74) 0.63 (0.157) 3.43 (0.853) 2.32 (0.579)