– 24 –
SM830078
4. COOLING CAPACITY
22
22
2 Indoor Unit: TS4232 Outdoor Unit: C4232, CL4232
• 208V / 1 phase / 60Hz
RATING CAPACITY : 40,500 BTU / h AIR FLOW RATE : 800 CFM
EVAPORATOR CONDENSER
ENT. TEMP. °F (°C) AMBIENT TEMP. °F (°C)
WB DB 75 85 95 105 115
(23.9) (29.4) (35.0) (40.6) (46.1)
TC 41,030 39,040 36,770 34,220 31,390
CI 2.97 3.24 3.53 3.95 4.37
72(22.2) SHC 28,050 26,900 25,620 24,230 22,740
59 76(24.4) SHC 30,910 29,760 28,490 27,100 25,610
(15.0) 80(26.7) SHC 33,910 32,760 31,490 30,100 28,600
84(28.9) SHC 36,780 35,630 34,360 32,970 31,390
88(31.1) SHC 39,650 38,500 36,770 34,220 31,390
TC 42,570 40,660 38,640 36,330 33,820
CI 3 3.29 3.58 4.01 4.44
72(22.2) SHC 24,250 23,240 22,190 21,020 19,800
63 76(24.4) SHC 27,120 26,100 25,060 23,890 22,660
(17.2) 80(26.7) SHC 30,120 29,100 28,060 26,890 25,660
84(28.9) SHC 32,990 31,970 30,930 29,760 28,530
88(31.1) SHC 35,850 34,840 33,790 32,630 31,400
TC 44,190 42,440 # 40,500 38,350 36,000
CI 3.02 3.31 3.62 4.05 4.48
72(22.2) SHC 20,430 19,580 18,660 17,660 16,600
67 76(24.4) SHC 23,290 22,450 21,530 20,530 19,470
(19.4) 80(26.7) SHC 26,290 25,450 24,520 23,530 22,470
84(28.9) SHC 29,160 28,310 27,390 26,400 25,340
88(31.1) SHC 32,030 31,180 30,260 29,270 28,210
TC 46,530 44,910 43,170 41,270 39,160
CI 3.06 3.35 3.67 4.11 4.55
72(22.2) SHC 16,690 15,980 15,220 14,410 13,540
71 76(24.4) SHC 19,560 18,850 18,090 17,280 16,410
(21.7) 80(26.7) SHC 22,560 21,840 21,090 20,280 19,400
84(28.9) SHC 25,430 24,710 23,960 23,150 22,270
88(31.1) SHC 28,300 27,580 26,830 26,020 25,140
TC 47,470 45,930 44,310 42,440 40,460
CI 3.11 3.4 3.73 4.17 4.61
75 76(24.4) SHC 15,350 14,740 14,110 13,390 12,650
(23.9) 80(26.7) SHC 18,350 17,740 17,110 16,390 15,650
84(28.9) SHC 21,220 20,600 19,970 19,260 18,520
88(31.1) SHC 24,080 23,470 22,840 22,130 21,390
TC : Total Cooling Capacity (BTU / h)
SHC : Sensible Heat Capacity (BTU / h)
CI : Compressor Input (kW)
Rating conditions are
: Outdoor Ambient Temp. 95 °F DB
: Indoor Unit Entering Air Temp. 80 °F DB / 67°F WB