8-1-3. Combustion Control
(1) Combustion
Combustion air is supplied into the burner for 20 seconds prior to ignition. The variable speed combustion air
blower motor speed is sensed and controlled. After this pre-purge is competed, spark ignition is provided at the
burner. Burner condition is monitored continuously during the burning period.
(2) Safety Controls
Following safety devices function to control the gas solenoid valve to shut off
Flame Detection Circuit: Stops gas flow with flame sensor circuit
Bimetal Thermostat: Stops gas flow with bimetal thermostat at 221°F (105°C)
Thermal Fuse: Stops gas flow with thermal fuse at 302°F (150°C) — replaceable fuse
Fuse-Control Circuit: Protected by internal 3A and 5A device
Exhaust
Refrigerant
heater
Supply
Gas inlet
Joint
Solenoid
valve 1
Solenoid
valve 2
Combination
gas valve
Flame sensor
probe
Ignition
electrical rod
Air
Combustion
blower fan
Ignition
circuit
Timer circuit
Pre-purge circuit
Combustion
blower motor
Flame sensor
circuit
Power
supply