8-1-3. Combustion Control
(1) Combustion
Combustion air is supplied into the burner for 20 seconds prior to ignition. The variable speed combustion air
blower motor speed is sensed and controlled. After this pre-purge is competed, spark ignition is provided at the
burner. Burner condition is monitored continuously during the burning period.
(2) Safety Controls
Following safety devices function to control the gas solenoid valve to shut off
● Flame Detection Circuit: Stops gas flow with flame sensor circuit
● Bimetal Thermostat: Stops gas flow with bimetal thermostat at 221°F (105°C)
● Thermal Fuse: Stops gas flow with thermal fuse at 302°F (150°C) — replaceable fuse
● Fuse-Control Circuit: Protected by internal 3A and 5A device