12-5. Flap Motor Does Not Work
12-5-1. Louver Motor Defective
Set to cooling operation with flap to oscillate (movie) using remote controller and measure voltage applied to
the louver motor at FLAP terminal of 5P connector.
In case of abnormality Replace indoor unit PCB.
No abnormalities, proceed to check
.
*Use a circuit tester (set to DC range).
Normal
Color Output Voltage
WHT and each BLU wire DC 1 – 12 V (pulse)
*Use a circuit tester (set to range).
Normal
Color Resistance
WHT and each BLU wire 300 – 450
Disconnect FLAP of 5P connector for louver motor and measure resistance.
In case of abnormality Replace louver motor.
No abnormalities, check if there is physical or mechanical interference to louver movement.
12-6. Heating Operation Not Possible
12-6-1. Thermistor 1 Defective
Failure Display on Outdoor Unit PCB: ●●
Check Thermistor 1 (CN15).
Disconnect Thermistor 1 connector (3P, BLK) from outdoor unit PCB, and measure resistance on Thermistor 1
side.
In case of abnormality Replace Thermistor 1.
Temperature Resistance
Normal
68°F (20°C) 6.0 – 7.1 k
86°F (30°C) 4.0 – 5.0 k
140°F (60°C) 1.5 – 1.7 k
Temperature Resistance
Normal
68°F (20°C) 6.0 – 7.1 k
86°F (30°C) 4.0 – 5.0 k
140°F (60°C) 1.5 – 1.7 k
12-6-2. Thermistor 2 Defective
Failure Display on Outdoor Unit PCB:
Check Thermistor 2 (CN16).
Remove Thermistor 2 connector (3P, RED) from the outdoor unit PCB, and measure resistance on the
Thermistor 2 side.
In case of abnormality Replace Thermistor 2.