Sanyo CG1411 User Manual Page 45

  • Download
  • Add to my manuals
  • Print
  • Page
    / 100
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 44
41
8-8. Overload Prevention (Heating)
8-8-1. Indoor Unit
This function prevents overheating of the indoor heat exchange coil.
When the temperature of the indoor heat exchange coil rises above 131°F (55°C), and if the indoor fan is
L (low speed), then the fan speed changes from L (low speed) to M (medium speed).
8-8-2. Outdoor Unit
Unless the temperature of Thermistor 1 drops to 144°F (62 °C) or less from the point A within 1 minute,
The burner is set to M (point C.)
Reset is activated when the temperature of Thermistor 1 drops to 122°F (50°C) or less, with the burner
being set to H.
High-load protection for the outdoor unit is operated independently from the high-load protection for the
indoor unit.
Compressor
Indoor fan
Indoor heat
exch.coil
temp.
HH, MM, LM
131°F
(55°C)
113°F
(45°C)
H or M or L
ON
Thermistor 1
149°F
(65°C)
144°F
(62°C)
122°F
(50°C)
Combustion
Compressor
H
M
L
C
A
B
H
1 minute
Stop
Page view 44
1 2 ... 40 41 42 43 44 45 46 47 48 49 50 ... 99 100

Comments to this Manuals

No comments