Sanyo CG1411 User Manual Page 36

  • Download
  • Add to my manuals
  • Print
  • Page
    / 100
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 35
32
8-2-2. Freeze Prevention (Cooling)
This function prevents freezing of the indoor heat exchange coil.
When the compressor has been running for 6 minutes or more and the temperature of the indoor heat
exchange coil falls below 36°F (2.4°C), the control circuit stops the compressor for at least 6 minutes. The
compressor does not start again until the temperature rises above 46°F (8°C) or 6 minutes have elapsed.
6 minutes
Set temp.
46°F
36°F
Compressor
Indoor heat exch.
coil temp.
Indoor fan
More than
3 minutes
More than
3 minutes
More than
10 minutes
Set speed
Page view 35
1 2 ... 31 32 33 34 35 36 37 38 39 40 41 ... 99 100

Comments to this Manuals

No comments